Square D Homeline Generator Interlock Kit & Inlet Wiring Guide
Connecting a 240V portable generator inlet (NEMA 14-50, L14-30, 14-30, or 6-50) to a Square D Homeline load center requires a mechanical interlock plate matched to the main breaker layout (HOMRBGK2C), a listed HOM 2-pole backfeed breaker, and a mechanical breaker hold-down retainer per NEC 408.36(D).
By Gil Sapir, Editor
Fast Answerβ‘ Interlock Reference: Square D Homeline Load CentersβΌ
Mechanical Interlock Kit (HOMRBGK2C) + HOM Backfeed Breaker
30A or 50A Double-Pole HOM Breaker β’ 6 AWG THHN Cu (50A Inlet) or 10 AWG Cu (30A Inlet)
Compatible Generator Inlet Configurations for Square D Homeline
Comparison of NEMA 14-50, 14-30, 6-50, and L14-30 generator inlets when wired to a Square D Homeline load center.
| Generator Inlet | Max Breaker / Amps | Continuous Load (80%) | Max Running Watts | Copper Wire Gauge | Pin Configuration |
|---|---|---|---|---|---|
| NEMA 14-50 (240V) | 50A 2-Pole (HOM) | 40A | 12,000 W peak | 6 AWG Cu (THHN) | 4-wire RV/Generator Inlet |
| NEMA 14-30 (240V) | 30A 2-Pole (HOM) | 24A | 7,200 W peak | 10 AWG Cu (THHN) | 4-wire Dryer/Generator Inlet |
| NEMA 6-50 (240V) | 50A 2-Pole (HOM) | 40A | 12,000 W peak | 6 AWG Cu (THHN) | 3-wire Welder/Generator Inlet |
| NEMA L14-30 (240V) | 30A 2-Pole (HOM) | 24A | 7,200 W peak | 10 AWG Cu (THHN) | 4-wire Twist-Lock Generator Inlet |
Square D Homeline Load Center Configurations & Interlock Reference Matrix
All 10 Square D Homeline panel variants, main bus ratings, branch breaker types, and interlock kit references.
| Panel Configuration | Main Rating | Branch Breaker Type | Interlock Reference Model |
|---|---|---|---|
| Square D Homeline 200A Main Breaker | 200A | Type HOM | HOMRBGK2C |
| Square D Homeline 100A Main Breaker | 100A | Type HOM | HOMCGK2C |
| Square D Homeline 125A Main Breaker | 125A | Type HOM | HOMCGK2C |
| Square D Homeline 150A Main Breaker | 150A | Type HOM | HOMCGK2C |
| Square D Homeline 200A Main Breaker | 200A | Type HOM | HOMRBGK2C |
| Square D Homeline 225A Main Breaker | 225A | Type HOM | HOMRBGK2C |
| Square D Homeline 100A Main Lug | 100A | Type HOM | HOMCGK2C |
| Square D Homeline 200A Outdoor | 200A | Type HOM | HOMRBGK2C |
| Square D Homeline 200A Plug-On Neutral | 200A | Type HOM | HOMCGK2C |
| Square D Homeline 40-Space 200A | 200A | Type HOM | HOMRBGK2C |
Generator NEMA 14-50 Inlet β Square D Homeline 200A Main Breaker Panel Wiring
Required Hardware Checklist for Square D Homeline
π§ Mechanical Interlock Kit (HOMRBGK2C)
Matched to Square D Homeline main-to-branch breaker spacing. Physically prevents turning on the generator backfeed breaker while the main utility breaker is closed.
Check Retailer Availability on Amazonπ Outdoor Generator Power Inlet Box (30A / 50A)
NEMA 3R weatherproof generator inlet box (NEMA 14-50 / CS6365 for 50A or NEMA L14-30 for 30A) wired to a listed 2-pole HOM backfeed breaker with hold-down kit.
Check Inlet Box Availability on AmazonRequired Wiring & Installation Accessories
50A Double-Pole Circuit Breaker
UL-Listed, mandatory for continuous EV charging load under NEC code.
6 AWG THHN Copper Wire (50ft Spool)
Heat-resistant 90Β°C copper conductor for conduit installation.
Hubbell HBL9450A / Bryant Electric 50A Industrial NEMA 14-50 Outlet
Industrial Grade heavy-duty receptacle (Hubbell HBL9450A / Bryant 50A). Mandatory safety upgrade to prevent melting on high continuous EV loads.
3/4" Schedule 40 PVC Conduit (10ft Lengths)
UV-resistant protection for exposed indoor/outdoor wire runs.
Generator Interlock Guides for Other Panel Lines
View NEC Article 702 interlock compatibility across other residential load center series:
Interlock Compatibility FAQ: Square D Homeline
Is a mechanical generator interlock kit compliant with NEC code for Square D Homeline panels?
Yes. Per NEC Article 702.5, a listed mechanical interlock plate physically prevents both the main utility breaker and the generator backfeed breaker from being turned on simultaneously in a Square D Homeline load center, and NEC 408.36(D) requires a mechanical hold-down retainer on the backfed plug-on breaker.
What size wire and breaker are required for a 50A or 30A generator inlet on a Square D Homeline panel?
A 50A generator inlet (NEMA 14-50 or CS6365) requires a 50A double-pole HOM-type breaker with 6 AWG THHN copper wire in conduit (or 6/3 NM-B where permitted). A 30A generator inlet (NEMA L14-30 or 14-30) requires a 30A double-pole HOM-type breaker with 10 AWG copper wire.
Which Square D Homeline panel ratings are covered on this page?
This guide covers all 10 residential Square D Homeline configurations, including Homeline 200A Main Breaker, Homeline 100A Main Breaker, Homeline 125A Main Breaker, Homeline 150A Main Breaker, Homeline 200A Main Breaker, Homeline 225A Main Breaker, Homeline 100A Main Lug, Homeline 200A Outdoor, Homeline 200A Plug-On Neutral, Homeline 40-Space 200A, using HOM branch breakers and reference interlock kit HOMRBGK2C.