Leviton Load Center Generator Interlock Kit & Inlet Wiring Guide

Connecting a 240V portable generator inlet (NEMA 14-50, L14-30, 14-30, or 6-50) to a Leviton Load Center load center requires a mechanical interlock plate matched to the main breaker layout (LLCIK20), a listed LB 2-pole backfeed breaker, and a mechanical breaker hold-down retainer per NEC 408.36(D).

By , Editor

Fast Answer⚑ Interlock Reference: Leviton Load Center Load Centers
β–Ό
πŸ† Reference Hardware Configuration

Mechanical Interlock Kit (LLCIK20) + LB Backfeed Breaker

⚑ Required Circuit & Conductors

30A or 50A Double-Pole LB Breaker β€’ 6 AWG THHN Cu (50A Inlet) or 10 AWG Cu (30A Inlet)

βœ“ Code Standard: NEC Article 702.5 & NEC 408.36(D) Backfed Breaker Hold-Down RuleRead Calculation Methodology →

Compatible Generator Inlet Configurations for Leviton Load Center

Comparison of NEMA 14-50, 14-30, 6-50, and L14-30 generator inlets when wired to a Leviton Load Center load center.

Generator InletMax Breaker / AmpsContinuous Load (80%)Max Running WattsCopper Wire GaugePin Configuration
NEMA 14-50 (240V)50A 2-Pole (LB)40A12,000 W peak6 AWG Cu (THHN)4-wire RV/Generator Inlet
NEMA 14-30 (240V)30A 2-Pole (LB)24A7,200 W peak10 AWG Cu (THHN)4-wire Dryer/Generator Inlet
NEMA 6-50 (240V)50A 2-Pole (LB)40A12,000 W peak6 AWG Cu (THHN)3-wire Welder/Generator Inlet
NEMA L14-30 (240V)30A 2-Pole (LB)24A7,200 W peak10 AWG Cu (THHN)4-wire Twist-Lock Generator Inlet

Leviton Load Center Load Center Configurations & Interlock Reference Matrix

All 10 Leviton Load Center panel variants, main bus ratings, branch breaker types, and interlock kit references.

Panel ConfigurationMain RatingBranch Breaker TypeInterlock Reference Model
Leviton All-Smart Load Center 200A200AType LBLLCIK20
Leviton All-Smart Load Center 100A100AType LBLLCIK10
Leviton All-Smart Load Center 125A125AType LBLLCIK12
Leviton All-Smart Load Center 150A150AType LBLLCIK15
Leviton All-Smart Load Center 200A200AType LBLLCIK20
Leviton All-Smart Load Center 225A225AType LBLLCIK22
Leviton Outdoor Smart Load Center 100A100AType LBLLCIK10
Leviton Outdoor Smart Load Center 200A200AType LBLLCIK20
Leviton Commercial Load Center 225A225AType LBLLCIK22
Leviton 42-Space Smart Load Center 200A200AType LBLLCIK20
Technical Wiring Schematic

Generator NEMA 14-50 Inlet β†’ Leviton All-Smart Load Center 200A Panel Wiring

⚠️ NEC 702.12 Interlock Rule
NEMA 14-50 Inlet240V / 50A Rating Conduit: 6 AWG THHN CopperLeviton All-Smart Load Center 200ABreaker: Type LBInterlock MechanicalPrevents Utility FeedbackDouble-Pole 50A
⚑
Mandatory National Electrical Code (NEC) Compliance:Under NEC 702.12, backfeeding a generator into a Leviton panel without a mechanical interlock kit is illegal and extremely dangerous to utility workers. Never connect a suicide cord directly to a live breaker without a verified LB-compatible interlock mechanism.

Required Hardware Checklist for Leviton Load Center

πŸ”§ Mechanical Interlock Kit (LLCIK20)

Matched to Leviton Load Center main-to-branch breaker spacing. Physically prevents turning on the generator backfeed breaker while the main utility breaker is closed.

Check Retailer Availability on Amazon

πŸ”Œ Outdoor Generator Power Inlet Box (30A / 50A)

NEMA 3R weatherproof generator inlet box (NEMA 14-50 / CS6365 for 50A or NEMA L14-30 for 30A) wired to a listed 2-pole LB backfeed breaker with hold-down kit.

Check Inlet Box Availability on Amazon
Installation Essentials

Required Wiring & Installation Accessories

Verified NEC Compatibility
Required Code$18.99

50A Double-Pole Circuit Breaker

UL-Listed, mandatory for continuous EV charging load under NEC code.

View Deal at Amazon
Top Rated Wire$64.50

6 AWG THHN Copper Wire (50ft Spool)

Heat-resistant 90Β°C copper conductor for conduit installation.

View Deal at Amazon
Fire Safety Must$79.00

Hubbell HBL9450A / Bryant Electric 50A Industrial NEMA 14-50 Outlet

Industrial Grade heavy-duty receptacle (Hubbell HBL9450A / Bryant 50A). Mandatory safety upgrade to prevent melting on high continuous EV loads.

View Deal at Amazon
Protection$12.40

3/4" Schedule 40 PVC Conduit (10ft Lengths)

UV-resistant protection for exposed indoor/outdoor wire runs.

View Deal at Amazon

Interlock Compatibility FAQ: Leviton Load Center

Is a mechanical generator interlock kit compliant with NEC code for Leviton Load Center panels?

Yes. Per NEC Article 702.5, a listed mechanical interlock plate physically prevents both the main utility breaker and the generator backfeed breaker from being turned on simultaneously in a Leviton Load Center load center, and NEC 408.36(D) requires a mechanical hold-down retainer on the backfed plug-on breaker.

What size wire and breaker are required for a 50A or 30A generator inlet on a Leviton Load Center panel?

A 50A generator inlet (NEMA 14-50 or CS6365) requires a 50A double-pole LB-type breaker with 6 AWG THHN copper wire in conduit (or 6/3 NM-B where permitted). A 30A generator inlet (NEMA L14-30 or 14-30) requires a 30A double-pole LB-type breaker with 10 AWG copper wire.

Which Leviton Load Center panel ratings are covered on this page?

This guide covers all 10 residential Leviton Load Center configurations, including All-Smart Load Center 200A, All-Smart Load Center 100A, All-Smart Load Center 125A, All-Smart Load Center 150A, All-Smart Load Center 200A, All-Smart Load Center 225A, Outdoor Smart Load Center 100A, Outdoor Smart Load Center 200A, Commercial Load Center 225A, 42-Space Smart Load Center 200A, using LB branch breakers and reference interlock kit LLCIK20.